Yaskawa A1000 Configuration for Crane Hoisting Application

15/10/2025

Requirements:

  • Control of a crane motor with specifications: 1.9/12.3 kW; 380-415V; 420/2830 rpm/min; 7.8/23.0 A. Power Factor (Cos Phi) 0.71/0.94; IP 54/55.

  • Operation with two fixed speed levels:

    • Speed Level 1: 13 Hz

    • Speed Level 2: 50 Hz

  • Starting and stopping using a ramp via a braking resistor.

Thông sốMô tảCài đặtMặc định
AInitialization
A1-02Control Method Selection[2] Open Loop Vector Control 1*[2] Open Loop Vector Control 1
A1-06Application Preset[6] Crane (hoist)*[0] General
BApplication
B1-01Frequency Selection[0] Digital Operater*[1] Control Circuit Terminal
B1-02Operation method selection[1] Control circuit terminal*[1] Control circuit terminal
B1-03Stopping method[0] Deceleration*[0] Deceleration
B6-01Dwell frequency at start3.0 Hz*0 Hz
B6-02Dwell time at start0.3 sec*0 sec
CTuning
C1-01Acceleration time 12.0 sec*10.0 sec
C1-02Deceleration time 15.0 sec*10.0 sec
C4-03Forward starting torque10.0 %*0.0 %
C4-04Reverse starting torque-10 %*0.0 %
C6-02Carrier frequency selection[02]*[1]
DReference Settings
D1-01Frequency reference 113 Hz*0 Hz
D1-02Frequency reference 250 Hz*0 Hz
D1-03Frequency reference 30 Hz*0 Hz
D1-04Frequency reference 40 Hz*0 Hz
D1-05Frequency reference 50 Hz*0 Hz
D1-06Frequency reference 60 Hz*0 Hz
D1-07Frequency reference 70 Hz*0 Hz
D1-08Frequency reference 80 Hz*0 Hz
D1-09Frequency reference 90 Hz*0 Hz
EMotor Prameter
E1-01Input voltage setting400 VAC*400 VAC
E1-03V/f pattern selection[OF]*[OF]
E1-04Max. output Frequency50.0 Hz*60.0 Hz
E1-05Max. voltage400 VAC*400 VAC
E1-06Base frequency50 Hz*60 Hz
E2-01Motor reted current23.0 A*26 A
E2-04Number of motor poles2*4
E2-11Motor rated output12.3 KW*15 KW
HTerminal Function Selection
H1-01Terminal S1 funtion selection[40] Forward run command*[40]
H1-02Terminal S2 funtion selection[41] Reverse run command*[41]
H1-03Terminal S3 funtion selection[03] Multi-step speed reference 1*[24]
H1-04Terminal S4 funtion selection[0F] Not used*[14]
H1-05Terminal S5 funtion selection[0F] Not used*[03]
H1-06Terminal S6 funtion selection[0F] Not used*[04]
H1-07Terminal S7 funtion selection[0F] Not used*
H1-08Terminal S8 funtion selection[0F] Not used*
H2-01Terminal M1/M2 Selection[0005]*[000] Closed: Output frequency is greater than or equal to value in L4-04 with hysteresis determined by L4-02
H2-02Terminal M3/M4 Selection[37] During frequency output*[001] Output frequency is zero
H2-03Terminal M5/M6 Selection[002]*[002] Outout frequency equals the speed reference
H3-02Terminal A1 Funciton selection[0F] Not used*[00] Frequency Bias
H3-06Terminal A3 Funciton selection[0F] Not used*[02] Auxiliary frequency reference 1
H3-10Terminal A2 Funciton selection[0F] Not used*[00] Frequency Bias
LProtection function selection
L2-03Min. baseblock time0.3 sec*1 sec
L3-04Stallp decelerarion selection[0] Disabled*[1] General purpose
L3-24Inertia conversion motor acceleration time0.265 sec*0.244 sec
L4-01Speed agreement level5 Hz*0 Hz
L4-02Speed agreement width0 Hz*2 Hz
L6-01Torque detection selection 1[8] Fault at run and inverter output is off*[0] Overtorque/ undertorque detection disabled
L6-02Torque detection lever 12 %150 %
L6-03Torque detection time 10.5 sec0.1 sec
L8-05Phase loss input selection[1] Enable*[0] Disable
L8-07Phase loss output selection[1] 1PH loss detection*[0] Disable
L8-38Carrier frequency time[1] Enable below 6 Hz*[2] Enable in whole speed range
L8-41Current warning[1] Enable*[0] Disable